GTV - Forced convection air heatersGTV - Forced convection air heaters

GTV - Forced convection air heaters
GTV air heaters are suitable for the heating of various types of spaces by being mounted on sidewalls, columns or the ceiling. The appliances equipped with axial or centrifugal fans either circulate the indoor air or suck in fresh air from outside. The appliances can be connected to an air duct both with the air supply and the exhaust side. The patented group burner design guarantees excellent combustion. The heat- and corrosion-resistant spatially bent heat exchangers of steel pipes ensure excellent heat transmission, their efficiency exceeds 91%.
Operation in closed mode can be carried out through the connection of various exhaustion and combustion air intake elements and sets. The options for mounting include bottom or top mounting, fixing on console with 4-point bolt connection, or suspension chains.

Version Nominal thermal input / Heating capacity output [kW]
GTV - Forced convection air heaters 20 GTV - Forced convection air heaters 27 GTV - Forced convection air heaters 33 GTV - Forced convection air heaters 40 GTV - Forced convection air heaters 48 GTV - Forced convection air heaters 58 GTV - Forced convection air heaters 68 GTV - Forced convection air heaters 78 GTV - Forced convection air heaters 87 GTV - Forced convection air heaters 97 GTV - Forced convection air heaters 107 GTV - Forced convection air heaters 116
GTV-A 18 24,3 29,7 36 43,2 52,2 62 71 80 89 98 106
GTV-C 18 24,3 29,7 36 43,2 52,2 - - - - - -
GTV-CL 18 24,3 29,7 36 43,2 52,2 - - - - - -

Design:

  • Patented group burner design
  • Heat- and corrosion-resistant steel pipe heat exchangers
  • Compact gas magnetic valve, ignition and flame monitoring
  • Exhaust fan solution
  • Available with axial or centrifugal fan
  • Adjustable shutters
  • Temperature control in summer and winter mode
  • Grouped regulation with pilot control
  • Industrial design with coloured housing
GTV-20A
Nominal thermal input (kW) 20
Heating capacity output (kW) 18
Gas consumption Natural gas G20 (m3/h) 2,12
Gas consumption Propane/Butane G30 (kg/h) 1,65
Exhoust/fresh air connection diameter (mm) ∅100 / 100
Gas connection 1/2"
Electrical connection 230V / 50Hz
Air flow (m3/h) 2000
Nominal electric input (A) 1,4
Electrical capacity (W) 300
Netto weight (kg) 58
DIMENSION - GTV-20A
GTV - Forced convection air heaters GTV - Forced convection air heaters GTV - Forced convection air heaters
A - appliance height (mm) 470
a - grid height (mm) 370
b - grid width (mm) 625
M - appliance depth (mm) 700
e - (mm) 135
 Back to Top